http://fancyprezzie.com

Pan yew  hp : 96580564

This Device is used to Monitor status of 8 inputs signal.  SMS up to 10 user if there is any change in input state.

 

Remote Monitoring via  GSM Modem SMS

 

 

1. Feature

·         10 programmable Handphone Number.

·         Send upon input change state

·         Monitoring up to 8 inputs

·         Total characters of 8 inputs Name must not more than 130 characters.

·         Each input Name  characters cannot exceed 24 characters.

·         SMS will report the input status in one shot.

·         SMS send upon Any input change state

·         Weekly or daily reporting

·         Programmable input Time delay

 

2. Power Up

     LCD display “ Press Enter to go Program Mode “

     Within  10 seconds, if Enter key is not pressed, it will automatically go to monitoring mode. Otherwise

     will go into program mode.

 

3. Monitoring Mode

    The LCD will display “ Monitoring

    The SMS  Monitoring Device will start monitoring.

    The SMS  Monitoring Device will send SMS to handphone if it detect  there is a change     

    In input state.

Once the message had send, the LCD will display fault status and start monitoring again.

 

Note : If you encounter keyboard hang, simply wait a while and type again. Backspace to delete.

 

4.Program Mode

 

4.1 Programming of parameter

Parameter

Value

 Description

SPARE

xx

  ignore

SPARE

xx

  ignore

Input Delay           

00 - 99 sec

Fault must be hold for that amount of duration before it is classified as fault

In_Config

00 or 99

00 for input Normally Close. 99 for input Normally open.

Loop

01 - 09

The number of time to send  SMS / pager .

Interval

00 -  99 min

The Time interval in minute to Re-send SMS  if Loop is not 01 

Mode

XX

 

Spare

xx

 

 

Example : To change the input delay from 01 sec to 05 sec, Press 05 Enter.

                 To remain as 01 sec, press Enter

 

 

 

 

4.3 Programming of handphone

       Prefix

C

For  sending SMS thru GSM modem

00

Ignore this number

 

       Example : Current 1st Num is C12345678. To change the handphone number to H88889999

                       Pressed H88889999. Enter

 

       Example : Current 1st Num is C11112222. Enter. To cancel the num, press 00 enter

 

4.4 Programming of  SMS message.

 

    Each SMS length must be not more  than 24 charactesr.

    The total number of Characters must not be more than 130 characters.

     Example :

     INPUT1_A is define as Power_Resume

     INPUT1_B is define as Power Failure

 

     INPUT2_A is define as Water no leak

     INPUT2_B is define as Water leak

 

     INPUT3_A is define as Aircon ok

     INPUT3_B is define as Aircon fail

 

     Prefix is define as AY1 Electronics

 

     Example :   Assume IN_CONFIG is programmed as 99, Normally open.

 

     LCD display “Monitoring “ followed by Date & Time

 

      If INPUT1 closed contact, Owner/user received

          

          AY1 Electronics Power Failure.

 

      LCD display “ Power failure”

 

      After sometimes, INPUT2 & 3 closed contact, Owner/user received

 

         AY1 Electronics Water leak, Aircon fail

 

      LCD display “Power failure” “Water leak “ “Aircon fail”

 

      After sometimes, INPUT1 open contact.Owner/user received

       

         AY1 Electronics Power Resume

 

      LCD display  Water leak “ “Aircon fail”

 

 

 

6. Full Programming Table

 

 

Parameter

Value

 Description

 

Spare

 

Any Number

F1

Spare

 

Any Number

 

Input Delay          

00 - 99 sec

Fault must be hold for that amount of duration before it is classified as fault

 

In_Config

00 or 99

00 for input Normally Close. 99 for input Normally open.

 

Loop

01 - 09

The number of time to send  SMS .

 

Interval

00 -  99 min

The Time interval in minute to Re-send  if Loop is not 01

 

Mode

XX

 

 

Spare

 

Any Number

 

Num 1

 

Phone number  Example :H12345678

F2

Num 2

 

Phone number

 

Num 3

 

Phone number

 

Num 4

 

Phone number

F3

Num 5

 

Phone number

 

Num 6

 

Phone number

 

Num 7

 

Phone number

F4

Num 8

 

Phone number

 

Num 9

 

Phone number

 

Num  10

 

Phone number

F5

IN_1A

 

Input 1 Alarm recovery message ( Max 24 character )

 

IN_1B

 

Input 1 Alarm message( Max 24 character )

F6

IN_2A

 

Input 2 Alarm recovery message ( Max 24 character )

 

IN_2B

 

Input 2 Alarm message ( Max 24 character )

F7

IN_3A

 

Input 3 Alarm recovery message ( Max 24 character )

 

IN_3B

 

Input 3 Alarm message ( Max 24 character )

 

IN_4A

 

Input 4 Alarm recovery message ( Max 24 character )

F8

IN_4B

 

Input 4 Alarm message ( Max 24 character )

 

IN_5A

 

Input  5 Alarm recovery message ( Max 24 character )

 

IN_5B

 

Input 5 Alarm message ( Max 24 character )

F9

IN_6A

 

Input 6 Alarm recovery message ( Max 24 character )

 

IN_6B

 

Input 6 Alarm message ( Max 24 character )

F9

IN_7A

 

Input 7 Alarm recovery message ( Max 24 character )

 

IN_7B

 

Input 7 Alarm message ( Max 24 character )

F10

IN_8A

 

Input 8 Alarm recovery message ( Max 24 character )

 

IN_8B

 

Input 8 Alarm message ( Max 24 character )

F11

PREFIX

 

Location  Message ( Max 24 character )

 

FSMSC